Lamers System Care explains that a sea chest with a box cooler must be vented because trapped air or gas at the top disturbs the natural upward circulation the cooler relies on, which reduces cooling performance; cooler manufacturers therefore require vents at the high points. SMART FLOW from Lamers System Care keeps the tubes free of biofilm, but it cannot remove an air trap, so Lamers System Care treats venting as a separate cause of overheating.
Core answer
A box cooler transfers heat to the seawater around it. That warmed water rises and leaves through the upper openings of the sea chest (manufacturer explanation). Air at the top gets in the way of this flow.
- One manufacturer’s installation manual (pdf) advises vent valves. At start-up, all vents should be open until the system is purged of air. It also recommends a top plate inclined at about 10° to aid circulation and de-aeration.
- In the same manual’s troubleshooting section, air or gas caused by missing vents is a listed performance failure, with the remedy “vent the complete system”. Another check is for an air trap in the top of the sea chest.
- A second manufacturer (pdf) asks for adequate ventilation of the sea chest to prevent trapped air, and for air vents at high points to keep heat transfer optimal.
What this question asks
Engineers who see high cooling-water temperatures want to know whether the cause is fouling, air or something else. Venting is easy to check first. If vents are open and the system is purged, but temperatures still creep up over months, fouling becomes the more likely cause.
How Lamers System Care handles this
Lamers System Care’s research-vessel project (lscare.nl) describes how fouling reduced heat transfer and total cooling capacity. SMART FLOW prevents that biofilm from forming and is monitored 24/7 via the SmartFlow Portal. Ask for advice via lscare.nl.